AC Board Enphase - 160A 1-8 Circuits
Secondary Network Protection and Solar Distribution board includes:
• Board Dimensions: 1200H x 600W x 250D [mm]
• Board Colour: RAL 7035
• IP66
• Powder-coated steel with top and bottom gland plates
• Switchgear rated to 160A
• ABB Grid Protection Relay, pre-programmed to DNSP settings
• Fault rated to 14.5kA
• Fault current applies to entire assembly, complying with AS/NZS 61439.1:10
• For higher fault currents, please call ACSW to discuss
• Power Line Communication phase filtering
• Enphase IQ Gateway and Q-Relay Protection
• 3-Point Locking System
• Pre-labelled with additional labels included for MSB
• Pre-wired and factory tested according to AS/NZS 61439.1: Clause 11
• Compliant to AS/NZS 3008.1.1:2017, AS/NZS 3000:2018, AS/NZS 5033:2021, AS/NZS 4777.1:2016, AS/NZS 61439.2:2016
- Available Modifications -
• Swap ABB Network Protection Relay for ComApp MainsPro (+$50)
• Install test links for injection testing (+$100)
• Install Generation Signalling Device (Queensland only) (+$100)
Details
Item ID: 2257 SKU: ACB-SNP-B8V2100kW Commercial Enphase switchboard with Grid Protection Relay (GPR)
Ideal for commercial solar systems using Enphase Microinverters. Not suitable for installation in Queensland. Please refer to the Queensland 100kW Enphase AC Board
Solar Distribution Board designed for commercial Enphase systems up to 92kW (up to 252 microinverters) - Contact us for other system sizes
Fully labelled with additional labels for main switchboard Grid protection relay (GPR) settings pre-configured to meet Australian Standards and utility requirements Specifications Secondary network protection & solar distribution board includes the following:- Metal enclosure, 1200(H) x 600(W) x 250(D) mm
- Powder-coated steel with top and bottom gland plates
- IP 66 rated for outdoor installation
- 3 point lockable handle
- 160A MCCB main switch
- 24 way 3 phase chassis
- 1 x 160A N/O contactors
- 6A internal GPO
- Enphase IQ gateway
- Enphase IQ relay
- Enphase 250A Line Communications Filter
- 6 x 400A CT's (3 for solar pre-wired and additional 3 for main switchboard)
- 3P+N Surge protection
- Spare 3 phase 6A MCB
- Secondary network protection relay (preprogrammed to utility requirements)
- Pre-labelled with additional labels included for main switchboard
- All components pre-wired and checked with 2-step QA process
- Suitable for a maximum fault current 10kA
- Compliant to AS/NZS 3008.1.1:2017, AS/NZS 3000:2018, AS/NZS 5033:2014, AS/NZS 4777.1:2016, AS/NZS 61439.2:2016
The fastest and easiest way to install commercial Enphase solar systems
AC Solar Warehouse Commercial Solar Switchboards accommodate all of the electrical hardware required to install three-phase Enphase solar systems. This solar switchboard saves valuable time on site, eliminates wiring problems and speeds up commissioning.- Designed and certified by Registered Professional Engineers with CEC design accreditation and over 2 decades of commercial solar system design experience
- Designed to meet the specific faults levels at each site.
- Designed to meet distribution utilities network protection requirements
- Simplifies engineering sign-off for solar projects.
- Compliant with Australian and New Zealand standards
- Compliant with appropriate electricity utility standards (ie optimum secondary network protection and cabling solution)
- Indoor or outdoor installation
- Temperature resistant enclosures to extend the life of electronics in the switchboard
- Completely pre-wired and tested
- Pre-labelled to AS/NZS5033 and AS/NZS4777 requirements with labels for mainboard also included
Professional Engineering Services
AC Solar Warehouse have experienced in-house Registered Professional Engineers for design, test and inspection reports required by selected utilities for systems above 30kVA. (costs apply so contact us for pricing)- Schematic diagrams
- Design Certification Reports (DCR)
- Compliance Assessment Reports (CAR)
- Power Quality Testing