Craftsman edition (With Gateway) - Installation Guide
The craftsman edition label kits are the culmination of years of iteration to reach our pièce de résistance. This label kit is the bees nuts.
Installers note: When the label plaque is installed outdoors, you must attach the provided engraved shutdown procedure, and yellow warning labels directly on top of the aluminium plaque to ensure compliance with AS/NZS 4777.1:2024 clause 6.1(c).
Installation SLD (BESS SECTION)
Gateway Layout Diagram - Home SP AU
Gateway Layout Diagram - Home TP AU
Gateway Layout Diagram - C60 AU
Installation SLD (ROOF SECTION, for the DC Coupled Kit)
Sigenergy BESS with Gateway Installed
|
Label |
Instruction |
|
1 |
| Included as part of the plaque, no overlay label is required due to this particular label not being stipulated in AS/NZS 4777.1 |
2 |
| Included as part of the plaque. Engraving of the battery short circuit current and max dc volts is required. set this as: Max D.C. Volts:
Short Circuit Current:
|
|
3 |
|
To be installed adjacent to the Sigenergy inverter and adjacent to the equipment to be operated in event of a shutdown (usually the switchboard the inverter is connected to).
|
|
* |
* Shall be installed above the text |
The warning sign must remain together with the associated warning text. Do not attach individually. Please follow the installation diagram for the correct placement. |
|
4 |
|
To be installed below each shutdown procedure label. |
|
5 |
|
Where both solar and a battery is installed, this label is to be installed adjacent to the Sigenergy inverter. |
|
6 |
|
To be installed on the white space on the bottom left hand side of the plaque (if you wish), or any other location you prefer. Not a required label so can be omitted. Engrave details as you wish or stick your own logo/sticker on top. |
|
7 |
|
When more than 1 battery system (stacks of batteries) is installed, this label is required to be installed adjacent to 1 of the inverters. Not required when only one battery system is installed. |
|
8 |
|
To be installed adjacent to each Sigenergy inverter. Label kit includes suitable labels if 2 battery systems are installed, if there are more, additional labels need to be sourced. |
|
9 |
|
To be installed adjacent to each DC Switch (under the left panel as per shutdown procedure) on the Sigenergy inverters. Label kit includes suitable labels if 2 battery systems are installed, if there are more, additional labels need to be sourced. |
|
10 |
|
When more than 1 battery system (stacks of batteries) is installed, these labels shall be installed adjacent to each Sigenergy inverter. Label kit includes suitable labels if 2 battery systems are installed, if there are more, additional labels need to be sourced. When only 1 battery system is installed, neither of these labels is required. |
|
11 |
|
If enclosed A.C. isolators are installed between the switchboard and the Sigenergy inverters, install these labels adjacent to the relevant isolator/s. |
|
12 |
|
To be installed on Sigenergy gateway (when installed) as the shutdown label references this. |
|
13 |
|
To be installed on Sigenergy gateway or other solar distribution board (when installed) between inverter and MSB as the label No. 34 references this. |
|
14 |
|
To be installed on the switchboard which the Sigenergy inverter is directly connected to. |
|
15 |
|
To be installed on MSB and all distribution switchboards electrically connected between the MSB and the switchboards to which the Sigenergy inverter is directly connected. 2 labels are provided in our kits, so if the Sigenergy inverter is connected to a switchboard other than the MSB and the switchboard which Sigenergy inverter directly connect, additional labels are required. |
|
16 |
|
Where the Sigenergy inverter is not connected directly to the MSB, this label is to be installed adjacent to the main switch of the switchboard it is connected to. |
|
17 |
|
To be installed adjacent to the Sigenergy bypass switch. |
|
18 |
|
To be installed adjacent to the contactor(s) in the Gateway. |
|
19 |
|
To be installed to the surge diverter in the Gateway. |
|
20 |
|
To be installed to the switch to which the generator is connected to. |
|
21 |
|
Identical to label 31. To be installed adjacent to the main isolator for the backup loads. If there is no main isolator for these loads (or there is no backup loads), this label is not required. - |
|
22
|
|
To be installed adjacent to each switch that the Sigenergy inverters are connected to (Sigenergy Gateway). Label kit includes suitable labels for 2 inverters, when more are installed, additional labels are required. |
|
23 |
|
To be installed adjacent to each switch that the Sigenergy inverters are connected to (Solar Distribution board/MSB). Label kit includes suitable labels for 2 inverters, when more are installed, additional labels are required. |
|
24 |
|
To be installed adjacent to the main isolator for the non-backup loads. If there is no main isolator for these loads (or there is no non-backup loads), this label is not required. |
|
25 |
|
To be installed adjacent to the main switch on the MSB. |
|
26 |
|
To be installed adjacent to the switch the power sensor is connected to. If no power sensor is installed, this label is not required. |
|
27 |
|
To be installed adjacent to the power sensor. If no power sensor is installed, this label is not required. |
|
28 |
|
To be installed adjacent to the switch the Sigenergy Gateway is connected to. If no gateway is installed, this label is not required. |
|
29 |
|
To be installed adjacent to the hot water main switch on the MSB. |
|
30 |
|
To be installed to the switchboard where the system is configured for whole home backup, or where all load circuits within the distribution board or switchboard are backed up. |
|
31 |
|
Identical to label 21. To be installed adjacent to the main isolator for the essential loads. If there is no main isolator for these loads (or there is no backup loads), this label is not required |
|
32 |
|
- To be installed adjacent to each backed-up circuit. |
|
33 |
|
To be installed on MSB. 1 label is provided in our kits. To be filled out. |
|
34 |
Safety Data Sheet |
To be installed on MSB or meter box and Fire panel. Please remove the irrelevant pages (if any) according to which battery modules have been installed. |
|
35 |
|
To be installed on MSB and main metering panel. Install the “SW” label on top of the “DP” where rooftop DC isolators are used instead of disconnection points. |
|
36 |
|
To be installed on MSB and main metering panel |
|
37 |
|
To be installed on MSB and all distribution switchboards electrically connected between the MSB and the switchboards to which the Sigenergy inverter is directly connected. Only required in Victoria. |
|
38 |
|
To be installed to the unused port (smart port and inverter port) on the Sigenergy Gateway. |
|
39 |
|
To be installed any location you prefer with the BESS area. |
Roof Section
|
40 |
|
Where DC cabling is installed within a ceiling space, this label is to be installed adjacent to the access point into the ceiling.
|
|
41 |
|
To be installed adjacent on each PV array d.c. isolator (not required if disconnection points are used instead of rooftop isolators). |
|
42 |
|
To be attached to the PV module or structure within 300mm of all disconnection points (not required if rooftop isolators are used instead of disconnection points). |
|
43 |
|
To be attached (typically zip tied) to positive and negative cables of all disconnection points (not required if rooftop isolators are used instead of disconnection points). |
Labels required for all installations, which are not included in our kit.
|
|
To be attached on DC cabling from the array to the inverter at intervals not less than 2m and at every change of direction. These labels are not included in the label kit and must be sourced separately. |
|
|
To be installed on MSB and fire panel shown on a plan (Map or drawing) when the battery system locations that are difficult to find or where the inverter (IES) is not within 3 meters and fully visible from the switchboard. This sign must indicate location of shutdown procedure and inverter. This label is not included in the label kit and must be sourced separately. |
|
|
To be installed on MSB and fire panel shown on a plan (Map or drawing). This label is not included in the label kit and must be sourced separately. |

