AC Board Pro - 400A Dual Inverter
Secondary Network Protection and Solar Distribution board includes:
• Metal Enclosure: 1200(H) x 600(W) x 250(D) [mm]
• Enclosure Colour: RAL 7035
• IP66
• Powder-coated steel with top and bottom gland plates
• Switchgear rated to 400A
• ABB Grid Protection Relay, pre-programmed to DNSP settings
• Fault current rated to 10kA
• Fault current applies to entire assembly, complying with AS/NZS 61439.1:10
• For higher fault currents, please call ACSW to discuss
• 2 x 200A Inverter MCCB's
• Spare 3 phase MCB
• Internal RCBO protected GPO
• Separate GPR supply and voltage reference
• Fuse protected monitoring
• 3-Point Locking System
• Pre-labelled with additional labels included for MSB
• Pre-wired and factory tested according to AS/NZS 61439.1: Clause 11
• Compliant to AS/NZS 3008.1.1:2017, AS/NZS 3000:2018, AS/NZS 5033:2021, AS/NZS 4777.1:2016, AS/NZS 61439.2:2016
- Available Modifications -
• Swap ABB Network Protection Relay for ComApp MainsPro (+$50)
• Install test links for injection testing (+$100)
• Install Generation Signalling Device (Queensland only) (+$100->200)
• Install 3P+N AC surge diversion (+$250)
Details
- Item ID :2258
- SKU: ACB-SNP-B11
Description
- Solar Distribution Board designed for 2 x SolarEdge, Sungrow or SMA inverters up to 110kW inverters each. Also suitable for most other inverter brands - Contact us for compatibility.
- Secondary network protection & solar distribution board includes the following:
- Metal enclosure, 1200(H) x 600(W) x 250(D) mm
- Powder-coated steel with top and bottom gland plates
- IP 66 rated for outdoor installation
- 3 point lockable handle
- 400A MCCB main switch
- 2 x 200A MCCB inverter circuit breaker
- 2 x 200A N/O contactor
- 6A internal GPO
- Spare 3 phase 6A MCB
- BB secondary network protection relay (preprogrammed to utility requirements)
- Pre-labelled with additional labels included for main switchboard
- Suitable for a maximum fault current of 11kA
- All components pre-wired and checked with 2-step QA process
- For higher fault currents, please call ACSW to discuss
- Compliant to AS/NZS 3008.1.1:2017, AS/NZS 3000:2018, AS/NZS 5033:2021, AS/NZS 4777.1:2016, AS/NZS 61439.2:2016
Have you considered REC 420W Alpha Pure R ? These modules are currently discounted to 39.5c/W while stocks last.